Three-Phase Integrated Lightning arrester

Three-Phase Integrated Lightning arrester
Product Detailed
Three-Phase Integrated Lightning arrester

Three-Phase Integrated Lightning arrester

Table1 FBP-A series Motor Type
Motor Rated voltage(KV) (r.m.s)6.310.5
lightning Rated voltage(KV) 7.612.7
Power frequency discharge voltage(KV) 15.025.0
Reference voltage at 1mA Dc(KV)(Crest)11.218.6
1.2/50μS Impulse discharge voltage(KV) 17.029.0
100A Swit ching current impulse(KV) 13.623.0
25KA Lightning current ipmulse(KV)17.029.0
2000μS Spupre wave Impulse curent(A) 400400
Safe net distaence()(mm)95120
furface Leakage distance()(mm)  140235
Smallest separate distance(mm)  115145
Table2 FBP-B series Vacuum Civcuit Breakev
System Voltage(KV) (r.m.s)61035
lightning Rated voltage7.612.742
Power frequency discharge voltage(KV)16.026.080.0
Reference voltage at 1mA Dc(KV)(Crest)14.42473
1.2/50μS Impulse discharge voltage(KV) 24.041.0124.0
500A Switching current impulse(KV) 19.032.099.0
2000μS Spupre wave Impulse curent(A) 400400400
Safe net distaence()(mm)95120285
furface Leakage distance()(mm) 1402351020
Smallest separate distance(mm)  115145470
Table3 FBP-C series Capacitor Type
System Voltage(r.m.s)61035
lightning Rated voltage(KV)7.612.742
Power frequency discharge voltage(KV)16.026.080.0
Reference voltage at 1mA Dc(KV)(Crest)14.42473
1.2/50μS Impulse discharge voltage(KV) 24.041.0124.0
500A Switching current impulse(KV) 19.032.099.0
2000μS Spupre wave Impulse curent(A)400400400
Safe net distaence()(mm)95120285
furface Leakage distance()(mm)  1402351020
Smallest separate distance(mm) 115145470
Table4 FBP-O series()
lightning Rated voltageMotorRated voltagelightningCurrent impulse Residual Voltage8/20us ≤ Reference Voltage at ImA Dc1mA IMA DC ≥
KV(rms)KV(rms)KV(crest)KV(crest)
4.86.312.06.8
810.519.011.4

Three-Phase Integrated Lightning arrester